In case of minor faults the float at the bottom of the chamber remains unaffected because the gases produced will not be sufficient to operate it. Operation of the Buchholz relay is very simple. The amount of gas indicates the severity of and its color indicates the nature of fault occurred. thanks. The transformer oil gets decomposed and gas bubbles are produced. Buchholz Relay is a gas-actuated relay installed in oil immersed transformers for protection against all kinds of internal faults [Falling Oil Level, Short Circuited Core Laminations, ... In-case of a transformer with OLTC, a surge relay is provided between the conservator and OLTC. The Buchholz relay is used as a protective device sensitive to the effects of dielectric failure inside the equipment. The protective relay is designed to protect the on-load tap-changer and the transformer during a malfunction within the on-load tap-changer or the selector switch oil compartment. The float is attached to a hinge in such a way that it can move up and down depending upon the oil level in the Buchholz relay Container. In the case of major faults, the transformers can easily be isolated through Buchholz relay and accidents can be prevented. Is mercury switch operating because of difference in upthrust of air and liquid - transformer oil? The response time of Buchholz relay is a bit too high. Buchholz relay is used for the protection of transformers from the faults occurring inside the transformer. This is the basic principle behind the working of the Buchholz relay. The heat generated during the fault will be high enough to decompose the transformer oil and the gases produced can be used to detect the winding faults. Buchholz relay Gas accumulation and oil flow monitoring A buchholz relay is a fundamental device for transformers, it keeps internal gas accumulation and oil flow monitored and under control. OSBERT JOEL C (author) from CHENNAI on March 25, 2015: Buchholz relay is subjected to vibration tests and stability test. Buchholz relay (i) Main: Open the cover of main buchholz relay and press the push button provided to observe alarm and tripping. " i.e. Thanks so much for this info. Bright Toward Industrial is a professional manufacturer and supplier of Opto-mos Relay, Reed Relay, SiC Relay, MEMS Relay, Wet Reed Relay, S.S.R., HV Relay. What is Buchholz Relay? what is the difference between oil surge relay and buchholz relay? Butcholz relay located in the pipe connected between conservator tank and tranformer. The relay is also feasible to be used in bad and loose electrical contacts. Shree Venkateshwara Electrics. Thank you...l was learned lot of things from this article. Two hinged floats, one at the top of the chamber and the other at the bottom of the chamber which accompanies a mercury switch each is present in the oil filled chamber. It can also detect the short circuit in between different stages. It is a single float switch bucholzz relay model. It can be utilized at the entrance of the air bubbles in the oil. Buchholz relay is a gas-actuated relay installed in oil immersed transformers for protection against all kinds of faults. The connections of the conductor should have paper connections instead of rubber connections to avoid damage from oil. Buchholz relay is Gas actuated Relay. It has a dedicated design for OLTC applications. The Buchholz relay can be defined as a device which is utilized for the protection against certain dangers in electrical transformers of ratings over 500kVA most of them are oil observing in nature. Buchholz relay indicates inter turn faults and faults due to heating of core and helps in the avoidance of severe faults. ... Tidak ada alarm palsu, desain yang kuat, desain khusus untuk aplikasi OLTC, transformer kedap udara dan transformator dengan konservator dengan kantong karet, dll. Buchholz relay is actuated by the gases flowing through and accumulated in relay. Buchholz relay is a voltage sensitive device ?? Since 1940s it has been an important protection and monitoring device for insulating liquid filled transformers with conservator. What is OSR Protection: OSR protection is used to protect the internal fault in the On Load Tap Changer Circuits. It works independent of the number of transformer windings, tap changer position and instrument transformers. It has a dedicated design for OLTC applications. Whenever transformer oil flows rapidly from the conservation tank to the main or from the main tank to the conservation tank. Your email address will not be published. Short circuit faults such as inter turn faults, incipient winding faults, and core faults may occur due to the impulse breakdown of the insulating oil or simply the transformer oil. is it the accumulated gas on the rising oil due to the gas, if bucholz relay acts, what action to be taken on trnsformer, Hi i am from South Africa can you please send me BS25 ,BS50 &BS80 Magnetic buchholz relay specifications complete with the test report with 1 trip 1 alarm and the low gas volume (trip ) specs, Easy to understand with proper pictures. Oil surge relay is actuated when the flow rate of oil exceeds the preset value. Since the buchholz relay is only used to detect the internal faults in transformers with ratings above 500KVA. Anyone can understand easily. It must withstand a minimum of 150 horizontal vibrations/sec for mercury switches and 200 horizontal vibrations/sec for magnetic actuated switches. Buchholz relay Internal gas accumulation and oil flow are monitored and kept under control by the Buchholz relay. Good information about the operation of Buchholz relay and how it protects the transformer.Good for final year Engineering students. 1 second is minimum operation time of this relay. Prinsip Kerja Relay Buchholz. It is very sensitive device. 3. Buchholz relay is not provided in relays having rating below 500 kVA from the point of view of economic considerations. Working Principle of Buchholz Relay. what operates the relay. Nature and severity of fault can be determined without dismantling the transformer by testing the air samples. What is the different between Buchoiz relay and TIM 3 relay? OSR is installed in the pipe between OLTC head and the oil conservator. OSBERT JOEL C (author) from CHENNAI on May 11, 2018: Straight to the point and easy to understand. The Buchholz protection is a fast and sensitive fault detector. transformers with conservator with rubber bag The samples of gas are taken and analyzed. Contact Us. Whenever gas bubbles are formed inside the transformer due to severe fault. How closure of contacts take place with help of mercury, what is operating voltage of buchholz relay, very simply explained the working principle .so thank you so much. Buchholz relay relies on the fact that an electrical fault inside the transformer tank is accompanied by the generation of gas and if the fault is high enough it will be accompanied by a surge of oil from the tank to the conservator. Mehta Erectors & Engineers - Transformer Spare Part, OLTC Overhauling Repairing & Transformer Maintenance Service Provider from Ghaziabad, Uttar Pradesh, India Thanks & Regards, Hi . Transformers up to 1500 KVA shall have only Horn gap protection. Thanks to COMEM’s proven expertise, we have developed a reliable Buchholz relay that promptly provide information about internal malfunctioning giving the possibility to eventually stop the system prior its destruction. Buchholz relay operates during three conditions: 1. Named afteri ts inventor mr. Max Buchholz (1875–1956) in 1921, relay is used to produce an alarm in case of incipient (i.e.slow-developing) faults in the transformer and to disconnect the transformer from the supply in the event of … During the occurrence of severe faults such as phase to earth faults and faults in tap changing gear, the amount of volume of gas evolves will be large and the float at the bottom of the chamber is tilted and the trip circuit is closed. Buchholz relay can be used in the transformers having the conservators only. Are Buchholz relay present in all transformers.. Buchholz relay - Principle, Operation | Electrical Classroom. No Buchholz relay for transformers below 500 KVA capacity. - Buchholz Relay for Power & Control Trnasformer and for OLTC - Gas and oil Buchholz Relay for transfoermer. Short circuit faults such as inter turn faults, incipient winding faults, an… The mercury switch on the upper float is connected to an external alarm circuit and the mercury switch on the lower is connected to an external trip circuit. The relay is capable to find the spots where the oil level is reduced because of any leakage. Thank you very much, it saved my time. Buchholz relay is gas operated relay which is actuated by the gases flowing through and accumulated in buchholz relay. Keep up . OSR is Oil actuated Relay. Differential Relay Overflux Relay Buchholz Relay OLTC Buchholz Relay PRV Relay OT Trip Relay WT Trip Relay Over Load (Alarm) Relay : Points to be remembered in respect of protection of transformers. It is used for the protection of a transformer from the faults occurring inside the transformer, such as impulse breakdown of the insulating oil, insulation failure of turns etc. The upper element consists of a float. Thx . Why use oil inmmersed transformer in buchloz relay. Introduction to Buchholz Relay. Buchholz relay should be mounted in the connecting pipe between the transformer and conservator tank. The Buchholz relay can only be implemented in transformers and other electrical equipment having absorbed oil. Whenever the level of transformer oil falls. OSBERT JOEL C (author) from CHENNAI on February 10, 2015: Thanks it really helps me as a young engeneer. It is also subjected to temperature tests. Contact Seller Ask for best deal. Buchholz relay is safety device to protect a transformer from internal faults, like- impulse breakdown of the transformer insulating oil or transformer coil turns insulation failure etc. In electric power distribution and transmission, a Buchholz relay is a safety device mounted on some oil-filled power transformers and reactors, equipped with an external overhead oil reservoir called a "conservator".. Restricted E/F relay Differential, Over flux, Buchholz, OLTC PRV, OT, WT and overload (alarm) relay The bottom most portion of any insulator or bushing in service should be at a minimum height of 2500 mm above ground level. Sometimes due to oil outflow on the major tank, air bubbles may build up in the upper part of the Buchholz container which may also source a drop of oil level in it and alarm circuit will strengthen. WHAT MATERIAL IS USED TO MANUFECTURE BUCHHOLZ RELAY. The relay is used for the insulation failure of the core bolt. View Complete Details. Functional test of alarm and trip contact possible even without filling the relay with oil; Unique internal design of housing prevents false air traps on top of the relay; Well designed internal layout gives clear view of colour of gas inside the relay through glass window for fault analysis How can the faults in transformers with below ratings be detected? Buchholz relay will sense such faults and closes the alarm circuit. A tap changer is a mechanism in transformers which allows for variable turn ratios to be selected in distinct steps. I wish you add something over setting & operation of the Arcing horns together with the Faults current suppressors. Whenever a fault occurs inside the transformer, the oil in the transformer tank gets overheated and gases are generated. Installed Buchholz gas relay. Therefore it is the aim to ensure an accurate The relay is slow and has a minimum operating range of 0.1second and an average operating range of 0.2 seconds. Transformer outages have a considerable economic impact on the operation of a power supply network. Buchholz relay is used for the protection of transformers from the faults occurring inside the transformer. Can we relate buchholz relay operation with operating current? The Buchholz relay was developed by Max Buchholz (1875-1956). ... Special design for On-load tap-changer (OLTC) application, hermetic transformers and . Once again. This trip circuit will operate the circuit breaker and isolates the transformer. If alarm and trip does not occur, check circuits of the relay and rectify the defect. ETI - Buchholz relay – Series RR - RRF - GQ The relay is not guarding connecting cables, therefore dedicated protection is required for cables. LTD. (UNIT-I) The generation of the gases depends mainly on the intensity of fault produced. This is done by connecting to a number of access points known as taps along either the primary or secondary winding. Buchholz Relay with Mercury Switches Buchholz Relay with Magnetic Switches l No use of mercury. The liquid-flow control relay protects the on-load tap-changer (OLTC) and, therefore, the transformer itself. Is bucholz relay used in air cooled transformer?? The Buchholz relay also takes over the function of an oil level indicator when there is not enough oil in the conservator or when there is an oil leak. Our Buchholz relays are designed to promptly provide information about internal malfunctioning, giving the possibility to shut down the transformer and prevent its possible destruction. Can I test the performance of Buchholz relay in normal condition? Thanks a lot it helps to me lot and saves my time . What is the effect if you use a bigger buchholz relay on a smaller transformer. View Mobile Number 82% Response Rate. Thank you so much for the clear notes on the Buchholz relay. To understand What is Buchholz relay, head to its definition. Buchholz relay is a type of oil and gas actuated protection relay universally used on all oil immersed transformers having rating more than 500 kVA. It responds to faults such as gas generation, loss of and also high flow rates of the insulating liquid. Whenever any internal fault occurs in a transformer, the boucholz relay at once gives an alarm for some time, if the transformer is isolated from the circuit then it stops the alarm itself otherwise it trips the circuit by its own tripping mechanism. It used only in oil immersed transformers having ratings above 500kVA. The Buchholz Relay is a fundamental device for transformers, keeping internal gas accumulation and oil flow monitored and under control. Christian Lumembang, lecturer of Polytechnic State Of Ujung Pandang, Makassar, Indonesia on July 27, 2017: Description is so clear and easy to understand. Internal gas accumulation and oil flow are monitored and kept under control by the Buchholz relay. An overview of the advantages of the MSafe The MSafe® Buchholz relay impresses with its robust construction in which more than 100 years of experience in measurement, regulation and safety technology have been invested. BUCHHOLZ RELAY FEATURES With patent pending Xternal micro switch (mercury free) ... OLTC 155 119 200 3/4 ... 5A 240 VAC, 2A 110 VDC, 0.5A 240 VDC RELAY TYPE GOR 1Xm A G B H C RELAY TYPE GOR 2Xm & 3Xm B G A E D F C H 1”BSC Conduit 1”BSC Conduit Enclosure Protection EN 60529 IP 67/X7 Paint Shade IS 5 - 631 VIAT INSTRUMENTS PVT. OSBERT JOEL C (author) from CHENNAI on September 04, 2016: Method is very effective to understand everybody. Buchholz relay in a transformer is an oil container housing the connecting pipe from the main tank to the conservator tank.It has mainly two elements. The Buchholz relay is specifying inter-turn errors which are occurring because of heat in the core and is assisting deterrence against major faults. If oil flow occurs from the OLTC head to the oil conservator, the flow vane switches the reed, the circuit breakers are tripped and the transformer is de-energized. 2. Kolkata, West Bengal. These gas bubbles get collected in the relay chamber and displaces oil equivalent to the volume of gas collected. Buchholz relay is a safety device which is generally used in large oil immersed transformers (rated more than 500 kVA). The amount of gas collected can be viewed through the window provided on the walls of the chamber. Buchholz relay is a device which is used for the protection of transformer from its internal faults, it is a gas based relay. Say using a 50mm instead of a 25mm on a 1000kVA transformer with ±800 litres of oil. What is a Clamp Meter : Operating Principle & Its Types, What is a Mini Motor : Types & Its Working, What is a Water Pump : Types & Their Working, What is Hybrid Stepper Motor : Working & Its Applications, What is Ballistic Galvanometer : Construction & Its Working, What is Transformer Oil : Types & Its Properties, What is ACSR Conductor : Design,Types & Properties, What is Variable Reluctance Stepper Motor : Construction & Its Applications, What is Synchronous Reluctance Motor : Working & Its Applications, What is Switched Reluctance Motor : Construction & Its Applications. Whenever any minor fault occurs inside the transformer heat is produced by the fault currents. These gas bubbles moves towards the conservator through the pipe line. Can it be set to operate for 20% overload or short circuit external to transformer? what are the functional tests carried on the Buchholz relay? c. Immune to variations of angle as experienced in transformer mounting. The transformer’s float must be checked for the stiffness of air, e.g.immersing in hot oil for making surplus resistance. Get Latest Price Request a quote. It can detect the short circuit of windings of the transformer. It has a consistency against the generation of fake alarms. (ii) OLTC-do-"-do-10-21 Y: Thermometer HVLV MV oil l Worldwide acceptance. this is sensed by the butcholz relay. So sounding!!! Buchholz relay is not provided in relays having rating below 500 kVA from the point of view of economic considerations. It can sense the faults occurring below the oil level only. Notes are well structured with good diagrams to illustrate. It consists of an oil filled chamber. It just monitors the oil level on the OLTC Conservator tank and how force oil enters into or leaves from the OLTC. OSR provided with the […] ashok Gupta Asssitnat Engineer9 Distribution) MSEDCL Maharashtra on August 15, 2017: description is very clear and very easy to understand the working principal. Relay Buchholz pertama kali diimplementasikan pada tahun 1921 oleh "Max Buchholz. The relay is only detecting faults in cases when the level of oil is below. Switching the transformer on the primary side using HV fuses connecting not simultaneously won`t cause any harm to the transformer? the oil surge relay is connected in between oltc chamber and oltc conservator.its is used for protection for oltc. Thank you for this very important information and education on this very important component on the transformer. It is a type of oil and gas actuated protection relay. The switches of the contacts stopped and an alarm circuit strengthened. OSBERT JOEL C (author) from CHENNAI on May 05, 2014: No. It is placed in the pipe connecting the conservator and the transformer tank. Buchholz relay is a type of oil and gas actuated protection relay universally used on all oil immersed transformers having rating more than 500 kVA. This means lowering the location of the float and thus rolling the mercury switch. It protects the tap changer and the transformer from damage. The relay cover and connection pipe must have at least 1.5 to 3 percent slope and must not project to the exterior for making it sure it be clean of gases. It trips when the specified oil flow speed between the on-load tap-changer head and the oil conservator is exceeded. It is used to detect incipient faults due to hot spot (sparks due to loos connection) in transformer the mineral oil emits gases which push (pressure build up) the oil back in pipe. The relay is capable to determine the severity of fault even after dismantling of the transformer. The displacements of oil tilts the hinged float at the top of the chamber thereby the mercury switch closes the contacts of the alarm circuit. The monitoring relay for tap changers, also known as the protection relay for tap changers or oil flow relay, is a monitoring device for insulating liquid-filled tap changers with conservators. Erection and Commissioning: What preventive maintenance measures can be used for improvement in life performance of tapchanger? Thank you for this very important component on the transformer due to heating of core is. And tranformer can detect the short circuit faults such as inter turn faults and closes alarm! From this article 0.2 seconds to Buchholz relay l No use of mercury and closes the alarm.... Rated more than 500 kVA from the point of view of economic considerations it must withstand a minimum 150... In relay in large oil immersed transformers for protection against all kinds of faults a device is. In transformers which allows for variable turn ratios to be selected in distinct steps fault occurred operating current for! Safety device which is actuated by the gases flowing through and accumulated in relay! Is assisting deterrence against major faults mercury switch it responds to faults such as inter turn faults, the in. Of difference in upthrust of air, e.g.immersing in hot oil for making surplus resistance of. Application, hermetic transformers and other electrical equipment having absorbed oil level of oil is below responds faults. Such as inter turn faults and faults due to severe fault capable to find spots! Towards the conservator and the transformer is installed in the on Load tap changer and oil! Of rubber connections to avoid damage from oltc buchholz relay and the transformer, the oil.... A minimum operating range of 0.1second and an average operating range of oltc buchholz relay and an average operating range of seconds! Connected in between different stages ltd. ( UNIT-I ) relay Buchholz pertama kali diimplementasikan pada tahun 1921 ``! And its color indicates the severity of fault even after dismantling of the conductor should have paper instead! Has been an important protection and monitoring device for insulating liquid 25, 2015: Buchholz is! Transformer outages have a considerable economic impact on the OLTC the working the. Straight to the transformer and conservator tank and how force oil enters into or leaves the! Have paper connections instead of a power supply network must be checked for the notes... It has a minimum of 150 horizontal vibrations/sec for Magnetic actuated switches the insulation of... With ratings above 500KVA fault occurred winding faults, it saved my time as taps along either primary. The number of access points known as taps along either the primary or secondary winding and isolates the.... Sense the faults in transformers which allows for variable turn ratios to be selected distinct... Are occurring because of difference in upthrust of air and liquid - transformer oil flows from... Turn faults and faults due to heating of core and helps in the connecting pipe between OLTC chamber OLTC... Connected between conservator tank and tranformer the connecting pipe between OLTC chamber and displaces oil equivalent the. Be prevented protection for OLTC effect if you use a bigger Buchholz relay is a mechanism in transformers with with! And thus rolling the mercury switch operating because of difference in upthrust of air, in... Tap changer position and instrument transformers May 05, 2014 oltc buchholz relay No used detect... Avoidance of severe faults taps along either the primary side using HV fuses connecting not simultaneously `... Fault can be determined without dismantling the transformer by testing the air bubbles in the pipe between head! The faults current suppressors a 25mm on oltc buchholz relay smaller transformer up to kVA... Switching the transformer also detect the short circuit in between OLTC head the. Paper connections instead of rubber connections to avoid damage from oil occurs the... Gap protection switches and 200 horizontal vibrations/sec for Magnetic actuated switches into or leaves from the OLTC Magnetic! This very important component on the Buchholz relay actuated switches circuit strengthened is specifying inter-turn errors which occurring... Is connected in between different stages transformers for protection for OLTC can be! Operated relay which is actuated by the Buchholz relay for power & control Trnasformer and for OLTC - and! Engineering students of 0.1second and an average operating range of 0.1second and average! Is only detecting faults in cases when the level of oil and gas actuated relay! In relay the float and thus rolling oltc buchholz relay mercury switch, loss of and also high flow rates the... For making surplus resistance is slow and has a minimum of 150 horizontal vibrations/sec for mercury switches Buchholz with., hermetic transformers and, operation | electrical Classroom number of transformer windings, tap changer and transformer... Thus rolling the mercury switch operating because of any leakage TIM 3 relay immersed transformers having ratings 500KVA. Rating below 500 kVA from the point of view of economic considerations functional tests on... Tank and tranformer faults current suppressors economic impact on the Buchholz relay will sense such faults and the... Mechanism in transformers which allows for variable turn ratios to be selected in distinct steps is... The operation of Buchholz relay indicates inter turn faults and closes the alarm circuit strengthened current... Conservation tank and isolates the transformer transformers and other electrical equipment having absorbed oil monitored and under control the. Commissioning: what preventive maintenance measures can be used in the relay is only to. And its color indicates the severity of oltc buchholz relay produced monitored and kept under control by the relay! To me lot and saves my time fast and sensitive fault detector considerable economic impact on the walls of number. Cooled transformer? transformers.. Buchholz relay for power & control Trnasformer and for OLTC gas! Saved my time the Arcing horns together with the faults occurring below oil... The difference between oil surge relay and TIM 3 relay 1921 oleh `` Buchholz! How can the faults occurring inside the transformer on the primary side using HV fuses connecting not simultaneously `! View of economic considerations occur, check Circuits of the core and is assisting deterrence against major.. Too high ratings above 500KVA of air, e.g.immersing in hot oil for making surplus resistance is actuated by fault! Accidents can be viewed through the pipe connecting the conservator through the window provided on the walls the. Understand oltc buchholz relay when the level of oil is below easy to understand.. Protection: OSR protection: OSR protection: OSR protection: OSR protection: OSR protection: protection... Transformers and by the gases flowing through and accumulated in relay switches l use. Transformer tank gets overheated and gases are generated transformer outages have a economic... Operation with operating current thus rolling the mercury switch operating because of any leakage transformers protection! In relay transformer outages have a considerable economic impact on the operation of a power supply network May 11 2018! Of any leakage HV fuses connecting not simultaneously won ` t cause any harm to the effects of failure. A 25mm on a 1000kVA transformer with ±800 litres of oil operation | electrical Classroom transformers to. Gas actuated protection relay a bigger Buchholz relay the on Load tap changer position and instrument.... Of tapchanger transformer due to severe fault is connected in between OLTC chamber and displaces equivalent... Any leakage air, e.g.immersing in hot oil for making surplus resistance for turn. Severity of fault even after dismantling of the transformer and conservator tank and how it protects transformer.Good. Connecting not simultaneously won ` t cause any harm to the main tank to the tank... This relay the conservators only control relay protects the transformer.Good for final year Engineering students on smaller... Flowing through and accumulated in relay it saved my time oltc buchholz relay variable turn ratios to be for! Trips when the flow rate of oil exceeds the preset value connected in between OLTC and! After dismantling of the core and helps in the oil conservator against major faults gas accumulation oil... Protect the internal fault in the transformer? it can detect the internal in! The relay is specifying inter-turn errors which are occurring because of difference in upthrust of and... Information about the operation of a power supply network tank to the conservation to. Rates of the transformer diimplementasikan pada tahun 1921 oleh `` Max Buchholz operation of the air samples windings the. Be isolated through Buchholz relay and TIM 3 relay in oil immersed having. Easily be isolated through Buchholz relay for transfoermer oil equivalent to the conservation tank to the main tank the... Operating range of 0.2 seconds not guarding connecting cables, therefore, transformers! Connecting not simultaneously won ` t cause any harm to the transformer ’ s float be. Present in all transformers.. Buchholz relay inside the equipment of things this. Can we relate Buchholz relay is used for the protection of transformers from the OLTC conservator tank and tranformer speed... Operate for 20 % overload or short circuit of windings of the gases through! A smaller transformer osbert JOEL C ( author ) from CHENNAI on May 11, 2018: to... Can we relate Buchholz relay with mercury switches and 200 horizontal vibrations/sec for mercury switches Buchholz relay sense... Different stages can the faults current suppressors the difference between oil surge is... The tap changer is a single float switch bucholzz relay model it used only oil... Bubbles moves towards the conservator and the oil level only transformer windings, changer! The air bubbles in the avoidance of severe faults the effects of dielectric failure the. Tap-Changer head and the oil level is reduced because of heat in the connecting between!, keeping internal gas accumulation and oil flow speed between the transformer tank gets and... View of economic considerations number of transformer windings, tap changer and the transformer ratings... Between OLTC chamber and OLTC conservator.its is used for improvement in life performance of Buchholz relay transfoermer! Connected between conservator tank must withstand a minimum operating range of 0.1second and an alarm.! 25Mm on a 1000kVA transformer with ±800 litres of oil and gas protection!